Mô tả sản phẩm
Product characteristics |
Electrical design |
PNP |
Output function |
2 x OSSD (A1 and A2) |
Housing |
threaded type |
Dimensions [mm] |
M12 x 1 / L = 70 |
Application |
Special feature |
Gold-plated contacts |
Type of operation |
continuous operation (maintenance-free) |
Application |
industrial applications |
Electrical data |
Operating voltage [V] |
19.2…30 DC |
Rated insulation voltage [V] |
30 |
Current consumption [mA] |
< 20 |
Protection class |
III |
Reverse polarity protection |
yes |
Max. power-on delay time [ms] |
1000 |
Outputs |
Electrical design |
PNP |
Output function |
2 x OSSD (A1 and A2) |
Max. voltage drop switching output DC [V] |
2.5; (30 mA) |
Permanent current rating of switching output DC [mA] |
100 |
Output data |
Interface type C class 1 |
Output voltage at 24 V |
compatible with EN 61131-2 inputs type 1, 2 |
Short-circuit protection |
yes |
Overload protection |
no |
Max. capacitive load CL_max [nF] |
20 |
Detection zone |
Enable zone [mm] |
0.5…4 |
Safe switching-off distance s(ar) [mm] |
6 |
Response times |
Response time to safety request [ms] |
1 |
Response time when approaching the enable zone [ms] |
1 |
Risk time (response time for safety-related faults) [ms] |
20 |
Operating conditions |
Applications |
class C to EN 60654-1 weatherproof application |
Ambient temperature [?C] |
-25…70 |
Note on ambient temperature |
operational life ? 87600 h |
|
Ambient temperature [?C] |
10…40 |
Note on ambient temperature |
operational life ? 175200 h |
|
Rate of temperature change [K/min] |
0.5 |
Max. relative air humidity [%] |
briefly: 5…95 %; permanent: 5…70 % |
Air pressure [kPa] |
80…106 |
Max. height above sea level [m] |
2000 |
Ionising radiation |
not permissible |
Salt spray |
no |
Protection |
IP 65; IP 67 |
Tests / approvals |
EMC |
IEC 60947-5-2 |
|
IEC 60947-5-3 |
|
EN 60947-5-3 |
|
EN 61000-4-2 ESD |
6 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated |
20 V/m |
EN 61000-4-4 Burst |
2 kV |
EN 61000-4-6 HF conducted |
10 V |
EN 61000-4-8 |
30 A/m |
EN 55011 |
class B |
|
Shock resistance |
|
Vibration resistance |
|
UL approval |
Ta |
-25…70 ?C |
Enclosure type |
Type 1 |
voltage supply |
Limited Voltage/Current |
File number UL |
E174191 |
|
Safety classification |
ISO 13849-1 |
category 2, PL d |
IEC 61508 |
SIL 2 |
IEC 62061 |
SIL cl 2 |
Mission time TM [h] |
? 175200 |
Mission time TM (additional indication) |
|
Safety-related reliability PFHD [1/h] |
1.0E-07 |
Mechanical data |
Weight [g] |
105.5 |
Housing |
threaded type |
Mounting |
non-flush mountable |
Dimensions [mm] |
M12 x 1 / L = 70 |
Thread designation |
M12 x 1 |
Materials |
stainless steel (1.4404 / 316L); PBT |
Displays / operating elements |
Display |
operation |
1 x LED, green |
signal |
1 x LED, yellow |
|
Accessories |
Accessories (supplied) |
|
Remarks |
Remarks |
Unless stated otherwise, all data refer to the reference target plate to IEC 60947-5-2 over the whole temperature range. |
(FE360 = ST37K) 12x12x1 mm |
|
Pack quantity |
1 pcs. |
Electrical connection – plug |
Connection |
Connector: 1 x M12; Contacts: gold-plated |