Mô tả sản phẩm
Electrical data |
Operating voltage [V] |
26.5…31.6 DC; (“supply class 2” to cULus) |
Max. current consumption from AS-i [mA] |
250 |
Max. current load total [A] |
2 |
Integrated watchdog |
yes |
Inputs / outputs |
Number of inputs and outputs |
Number of digital inputs: 4; Number of digital outputs: 4 |
Inputs |
Number of digital inputs |
4 |
Input circuit of digital inputs |
PNP |
Sensor supply of the inputs |
AS-i |
Voltage supply [V] |
18…30; (via flat cable) |
Max. total current rating of inputs [mA] |
200 |
Input current High [mA] |
6…10 |
Input current Low [mA] |
0…2 |
Min. switching level high signal [V] |
11 |
Digital inputs protected against short circuits |
yes |
Outputs |
Number of digital outputs |
4 |
Circuit |
PNP |
Voltage range DC [V] |
15…30; (to PELV; via flat cable) |
Max. current load per output [mA] |
1000; (utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1)) |
Short-circuit proof |
yes |
Electrically separated |
yes |
Operating conditions |
Ambient temperature [?C] |
-25…70 |
Protection |
IP 67 |
Tests / approvals |
EMC |
|
MTTF [years] |
155 |
AS-i classification |
AS-i version |
2.11 + 3.0 |
AS-i addressing |
addressing socket |
Extended addressing mode possible |
no |
AS-i profile |
S-7.0.E |
AS-i I/O configuration [hex] |
7 |
AS-i ID code [hex] |
0.E |
AS-i certificate pending |
yes |
Assignment of the data bits |
data bit |
D0 |
D1 |
D2 |
D3 |
input |
1 |
2 |
3 |
4 |
socket |
I-1 |
I-2 |
I-3 |
I-4 |
pin |
2+4 |
2+4 |
2+4 |
2+4 |
Output |
1 |
2 |
3 |
4 |
socket |
O-1/2 |
O-1/2 O2 |
O-3/4 |
O-3/4 O-4 |
pin |
4 |
2 4 |
4 |
2 4 |
|
Mechanical data |
Weight [g] |
309 |
Type of mounting |
AS-i flat cables directly connectable |
Materials |
PA; piercing contacts: CuSn6 nickel-plated and tin-plated |
Displays / operating elements |
Display |
operation |
LED, green |
errors |
LED, red |
function |
LED, yellow |
|
Accessories |
Accessories (supplied) |
|
Accessories (optional) |
Protective cap: M12, E73004 |
|
Remarks |
Remarks |
Inputs and outputs must be electrically isolated. |
Do not connect any of the following points to an external potential: |
I-, I+, I1, I2, I3, I4 |
The connections are electrically connected with the AS-i cable. |
|
Pack quantity |
1 pcs. |
Electrical connection |
|
quick mounting technology for AS-i flat cable: ; three orientations possible |
Electrical connection – Inputs |
|
Connector: M12 |
Electrical connection – Outputs |
Connection |
Connector: M12 |