Mô tả sản phẩm
Electrical data |
Operating voltage [V] |
26.5…31.6 DC |
Max. current consumption from AS-i [mA] |
450 |
Reverse polarity protection |
yes |
Inputs / outputs |
Number of inputs and outputs |
Number of analogue inputs: 4 |
Inputs |
Number of analogue inputs |
4; (Anschluss von 2-, 3-, 4-Draht-Sensoren) |
Sensor supply of the inputs |
AS-i |
Digital inputs protected against short circuits |
yes |
Analogue input (current) [mA] |
4…20 |
Max. voltage drop across load for nominal voltage [V] |
10 |
Resolution of analogue input |
12 bit |
Operating conditions |
Ambient temperature [?C] |
-5…70 |
Protection |
IP 68; IP 69K |
Tests / approvals |
EMC |
|
MTTF [years] |
98 |
AS-i classification |
AS-i version |
2.11 + 3.0 |
Extended addressing mode possible |
no |
AS-i profile |
S-7.3.E |
AS-i I/O configuration [hex] |
7 |
AS-i ID code [hex] |
3.E |
AS-i certificate |
101108 |
Mechanical data |
Weight [g] |
625 |
Dimensions [mm] |
137.3 x 80 x 137.3 |
Materials |
threaded bush: stainless steel (1.4404 / 316L); PC; O-ring: EPDM |
Displays / operating elements |
Display |
operation |
LED, green Voltage AS-i |
errors |
LED, red |
function |
LED, yellow channels AI1…AI4 |
|
Accessories |
Accessories (optional) |
Protective cap: M12, E70297 |
Flat cable insulation displacement connector, E70454 |
Torque wrench, E70390 |
|
Remarks |
Remarks |
When the sensors and actuators are supplied from AS-i the load must not exceed a maximum of 380 mA. |
The load for an individual sensor connection must not exceed 200 mA. |
When connecting a 2-wire or 3-wire sensor without own supply there has to be an external link between pin 3 and pin 4. |
The inputs (pins 2 and 4) are electrically separated and have no connection to AS-i. |
The sensor supply (pins 1 and 3) is electrically connected to AS-i. |
|
Pack quantity |
1 pcs. |
Electrical connection – AS-i |
|
Connector: 1 x M12 |
Electrical connection – Process connection |
|
Connector: 4 x M12 |