DCS800 |
|
Mains supply |
|
Voltage – power part, 3-phase |
230V to 1000V in acc. with IEC 60038, higher voltage is available on request. |
Voltage deviation |
+/- 10% continuous |
Rated frequency |
50Hz or 60Hz |
|
|
Voltage – field exciter |
110 to 500V, 1 ph for units 6…50Adc |
Voltage deviation |
+/- 10% continuous |
Frequency range |
50Hz or 60Hz |
|
|
Voltage – aux. supply, 1-phase |
115V / 230V in acc. with IEC 60038 |
Voltage deviation |
-15% / +10% |
Frequency range |
45Hz to 65Hz |
|
|
Voltage – fan supply |
115V/230V, 1 ph … 690V, 3 ph depending on frame sizes. |
|
|
Degree of protection
as DCS800-A Enclosed Conv.
as DCS800-E Panel Solution |
IP 00
IP20 / IP21 / IP31 / IP41
IP20 |
|
|
|
|
DC outputs |
|
DC voltage |
The maximal DC voltage is depending on supply voltage and converter type (2Q or 4Q). If a 2Q unit is also used in regenerative mode, please use also the values of the 4Q column. The following classes are available with the recommended DC voltage:
AC supply |
|
DC voltage |
|
|
2Q
|
|
4Q
|
230V
400V
|
|
265V
465V
|
|
240V
415V
|
500V
|
|
580V
|
|
520V
|
600V
|
|
700V
|
|
625V
|
690V
|
|
800V
|
|
720V
|
790V
|
|
915V
|
|
820V
|
990V
|
|
1160V
|
|
1040V
|
1200V
|
|
1380V
|
|
1235V
|
|
|
|
DC current |
According rated current of frame sizes:
20 … 260A
|
|
D1, D2 with supply up to 525Vac |
350 … 1000A
|
|
D3, D4 with supply up to 525Vac/600Vac |
900 … 2000A
|
|
D5 with supply up to 690Vac |
1900 … 3000A
|
|
D6 with supply
up to 800Vac |
2050 … 5200A
|
|
D7 with supply
up to 990/1200Vac |
> 5200A
|
|
higher current is available on request. |
|
|
|
DC field voltage |
Max. field voltage 110V to 500V, depending on supply voltage and field exciter unit. |
|
|
|
6/15/20/25A
|
|
Field exciter onboard of D1/D2/D3/D4 |
25A
|
|
Internal with FEX-425-INT for D5 as option |
35A
|
|
Field exciter DCF80x (external) |
> 35A
|
|
on request |
|